D.01

Terrace parapet

Peto de cubierta
217 mm
Total thickness · Revision 01 · 2026-08
D.01 Terrace parapet SCALE 1:10
1 2 mm 2 15 mm 3 140 mm 4 5 mm 5 50 mm 6 5 mm 217 mm Int. · terrace face Ext.

Keyboard navigable with the arrow keys; the same data is published as a table in the layer schedule below.

Photographs

1 / 3

Layer schedule

D.01 · layer schedule · total 217 mm
Layer Material Thickness λ Function
1 Monocapa render Single-coat mineral render 2 mm — Finish to the terrace face
2 Aquapanel cement board Cement-bonded board 15 mm — Substrate and rigid sheathing to the terrace face
3 Steel C-stud zone Cold-formed galvanised steel 140 mm — Structure No fill is called out for this zone on the section drawing.
4 Placner ribbed sheet Cold-rolled galvanised steel, Z200, 0.3 mm base sheet 5 mm — Substrate and mechanical key for the sprayed layer 5 mm is the overall profiled depth including rib height, not the sheet gauge.
5 INSULTERM 600, sprayed Sprayed thermal-acoustic conglomerate 50 mm 0.138 W/m·K Continuous external insulation
6 Monocapa render Single-coat mineral render 5 mm — External weather finish
Total 217 mm

An em dash means the source document does not state that value; it is not a zero. Cavity-contained layers are indented — they sit inside the stud depth, so the column does not sum to the total.

The parapet that closes the terrace edge. Its cavity is uninsulated, and deliberately so: the parapet sits outside the thermal envelope, where insulation would do no work. Read without that explanation the detail looks like an omission, which is why it is stated here rather than left to inference.

Calculated performance

D.01 · performance
Property Value Basis
Self-weight 71 kg/m² Mass estimate from the layers and dimensions in the source document.
Traditional equivalent 254 kg/m² Derived from the published self-weight and reduction percentage.
Weight reduction −72% Self-weight against the traditional equivalent build-up.
Fire resistance (EI) Test programme in progress — contact technical department Awaiting laboratory test report
Airborne sound reduction (R_A) Test programme in progress — contact technical department Awaiting laboratory test report
Watertightness Test programme in progress — contact technical department Awaiting laboratory test report

Not yet stated

  • EIFire resistance · in test
  • R_AAirborne sound reduction · in test
  • watertightnessWatertightness · in test

Test programme in progress — contact technical department

Weight against traditional

Element Solid System Traditional Reduction
D.01 Terrace parapet 71 kg/m² 254 kg/m² −72%

Where to use it

  • Terrace and flat-roof perimeter upstands
  • Roof edge closures where the parapet falls outside the insulated envelope

Design notes

  • The cavity is uninsulated because the parapet sits outside the thermal envelope. This is a design decision, not an omission.
  • Aquapanel must not be substituted with standard plasterboard on the parapet.
  • Coping and roof turn-up are project-specific and are detailed per scheme.

Downloads

DWG D.01 section drawing In preparation
PDF D.01 section drawing In preparation
CSV D.01 layer schedule