D.04

Internal partition

Tabique interior
146 mm
Total thickness · Revision 01 · 2026-08
D.04 Internal partition SCALE 1:10
1 13 mm 2 15 mm 6 90 mm 7 15 mm 8 13 mm 3 25 mm 4 40 mm 5 25 mm 146 mm Int. Int.

Dashed layers sit inside the stud cavity, not in addition to it. Keyboard navigable with the arrow keys; the same data is published as a table in the layer schedule below.

Photographs

1 / 14

Layer schedule

D.04 · layer schedule · total 146 mm
Layer Material Thickness λ Function
1 Pladur plasterboard lining Gypsum board 13 mm — Internal finish
2 Omega furring profile Cold-formed galvanised steel 15 mm — Decoupled fixing profile for the lining, with a service void
3 INSULTERM 600 in stud cavity Sprayed thermal-acoustic conglomerate 25 mm 0.138 W/m·K Encapsulation
4 Mineral wool in stud cavity Rock wool 40 mm 0.039 W/m·K Acoustic core ISOVER Alphatoit rigid rock wool panel, as in D.02. λD from the manufacturer's datasheet (FT_Alphatoit_ES, 14/03/2024), to EN 12667 / EN 12939.
5 INSULTERM 600 in stud cavity Sprayed thermal-acoustic conglomerate 25 mm 0.138 W/m·K Encapsulation
6 C90 steel stud cavity Cold-formed galvanised steel 90 mm — Framing — the cavity contains layers 3, 4 and 5
7 Omega furring profile Cold-formed galvanised steel 15 mm — Decoupled fixing profile for the lining, with a service void
8 Pladur plasterboard lining Gypsum board 13 mm — Internal finish
Total 146 mm

An em dash means the source document does not state that value; it is not a zero. Cavity-contained layers are indented — they sit inside the stud depth, so the column does not sum to the total.

The non-load-bearing internal partition, on C90 studs. At 146 mm it is the thinnest of the vertical elements after the wet-area partition, and it is the detail that appears most often on a residential floor plate.

Calculated performance

D.04 · performance
Property Value Basis
U-value, bridging corrected 0.55 W/m²K EN ISO 6946, one-dimensional steady state, with a +20% bridging correction applied as an engineering estimate.
Self-weight 62 kg/m² Mass estimate from the layers and dimensions in the source document.
Traditional equivalent 89 kg/m² Derived from the published self-weight and reduction percentage.
Weight reduction −30% Self-weight against the traditional equivalent build-up.
Fire resistance (EI) Test programme in progress — contact technical department Awaiting laboratory test report
Airborne sound reduction (R_A) Test programme in progress — contact technical department Awaiting laboratory test report
Impact sound (L_nw) Test programme in progress — contact technical department Awaiting laboratory test report

U-values are one-dimensional steady-state calculations to EN ISO 6946. Bridging correction is applied as an engineering estimate: +20% for walls, +15% for horizontal elements. 2D numerical analysis to EN ISO 10211 is in progress; values will be updated on completion.

Not yet stated

  • EIFire resistance · in test
  • R_AAirborne sound reduction · in test
  • L_nwImpact sound · in test

Test programme in progress — contact technical department

Weight against traditional

Element Solid System Traditional Reduction
D.04 Internal partition 62 kg/m² 89 kg/m² −30%

Where to use it

  • Non-load-bearing partitions within a dwelling
  • Room divisions on C90 studs

Design notes

  • C90 studs are specified for partitions. C140 is used for load-bearing walls and façades.
  • Services are run within the stud cavity before the lining is closed.

Downloads

DWG D.04 section drawing In preparation
PDF D.04 section drawing In preparation
CSV D.04 layer schedule